solar inverter repair

Solar Inverter Fire in Bangholme: Burning Smell, Then Smoke

Suburb/Industry: Bangholme, Victoria

Size of solar installation: 99kW ground mounted solar installation or 300 panel system.

Age: 6 years old

Problem: The business owner worked near the utility shed that housed the solar system’s inverter. He noticed a burning smell and saw black smoke coming from the shed, then heard a loud bang. As a result, this solar inverter fire blew the inverter cover off the box and sent it 4 metres across the shed, blowing a hole in the opposite wall.

Cause: Inside the terminal box (sitting below the inverter), you can clearly see the fire damage. The AC terminal block is severely burnt, and the DC terminal block no longer exists. In addition, contact points are visible along the cabling. This suggests either a failed terminal block or a loose connection created a hot spot, which then caused the inverter fire.

Impact: This solar inverter fire caused significant physical damage and created a serious hazard, as the inverter cover became a projectile inside the utility shed. The system therefore stopped generating solar energy, which led to financial loss. This resulted in approximately $2,520 per week in lost energy production.

Solution: For safety, technicians shut the system down immediately. They replaced the inverter, cabling, and terminal block as part of a full solar inverter fire repair, restoring the system with new components.

Annual servicing is recommended for commercial solar installations. While it is difficult to predict every failure, a regular service & maintenance program can identify loose connections and faults early. As a result, this reduces the risk of future incidents and the need for solar inverter fire repair.

solar inverter repair
solar inverter repair

Contact The Solar Repair Man today for professional solar inverter repairs and preventative maintenance.