Job: Commercial Rooftop Solar Fire
Suburb: Cheltenham, Victoria
Size of Solar Installation: 400 panels
Problem: At the site, a Factory Fire occurred due to water accumulating inside the DC rooftop isolation switches of the solar system. Poor sealing of the switches and incoming conduits during installation allowed water to enter. Over time, this created a serious risk of electrical faults.
Impact: Water reached the DC cable connections inside the switches. This caused a DC short circuit, which ignited a fire on the rooftop. The fire damaged one solar panel, four DC isolation switches, associated wiring, and the 25KW 3-phase inverter. Fortunately, the fire stayed contained, limiting the damage to these components.
Action Taken: Our team responded immediately to secure the site. We removed the burnt components and replaced the damaged panel, inverter, isolation switches, and wiring. After repairs, we tested the system to ensure it worked safely and efficiently.
During the process, we also inspected the full solar array. This ensured no hidden faults remained and confirmed compliance with safety standards.
Outcome: The Factory Fire highlights the risks of poor sealing and neglected maintenance. Regular inspections could have prevented water ingress and avoided significant damage. Businesses with rooftop solar systems should schedule routine servicing to ensure safety and efficiency.